Parameter Descriptions
30-05 Wobble Jump Frequency [%]
Range:
0 %
[0 -
*
100 %]
3
3
30-06 Wobble Jump Time
Range:
Size related
*
s]
30-07 Wobble Sequence Time
Range:
10 s
[1 - 1000 s] This parameter determines the wobble
*
30-08 Wobble Up/ Down Time
Range:
5 s
[0.1 - 1000 s] Defines the individual up and down times
*
30-09 Wobble Random Function
Option:
[0]
*
[1]
3.21.2 Center Frequency
Use parameter group 3-1* References to set the center
frequency.
30-10 Wobble Ratio
Range:
1
[0.1 - 10] If the ratio 0.1 is selected: t
*
30-11 Wobble Random Ratio Max.
Range:
10
[ par. 17-53 - 10] Enter the maximum allowed wobble
*
30-12 Wobble Random Ratio Min.
Range:
0.1
[ 0.1 - par. 30-11] Enter the minimum allowed wobble
*
210
Function:
The jump frequency can also be expressed as
percentage of the center frequency. The
function is the same as for
parameter 30-04 Wobble Jump Frequency [Hz].
Function:
[ 0.005 - 5.000
This parameter determines the
slope of the jump ramp at the
maximum and minimum wobble
frequency.
Function:
sequence period. This parameter can only be
changed in stop mode.
Wobble time = t
+ t
up
down
Function:
for each wobble cycle.
Function:
Off
On
Function:
is 10 times
down
greater than t
.
up
If the ratio 10 is selected: t
is 10 times greater
up
than t
.
down
Function:
ratio.
Function:
ratio.
Danfoss A/S © 01/2018 All rights reserved.
®
VLT
AutomationDrive FC 301/302
30-19 Wobble Delta Freq. Scaled
Range:
0 Hz
*
3.21.3 30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
Range:
Size related
30-21 High Starting Torque Current [%]
Range:
Size related
30-22 Locked Rotor Protection
Option: Function:
[0] Off
[1] On
30-23 Locked Rotor Detection Time [s]
Range:
Size related
Function:
[0 - 1000 Hz] Readout parameter. View the actual
wobble delta frequency after scaling has
been applied.
Function:
NOTICE
[0 - 60 s]
*
This parameter is available for FC
302 only.
High starting torque time for PM motor
in flux control principle without
feedback.
Function:
NOTICE
[ 0 -
*
200.0 %]
This parameter is available for
FC 302 only.
High starting torque current for PM
motor in VVC
without feedback.
NOTICE
This parameter is available for FC 302 only.
Available for PM motors only, in flux sensorless mode
and VVC
+
open-loop mode.
Protects the motor from the locked rotor condition. The
control algorithm detects a possible locked rotor
condition in the motor and trips the frequency
converter to protect the motor.
Function:
[0.05 - 1 s] Time period for detecting the locked
*
rotor condition. A low parameter
value leads to faster detection.
+
and flux mode
MG33MO02