Parameter Descriptions
5-93 Pulse Out #27 Bus Control
Range:
Function:
0.00 %
[0.00 -
Set the output frequency transferred to
*
100.00 %]
output terminal 27 when the terminal is
configured as [45] Bus Controlled in
parameter 5-60 Terminal 27 Pulse Output
Variable.
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0.00 %
[0.00 -
Set the output frequency transferred to
*
100.00 %]
output terminal 27 when the terminal is
configured as [48] Bus Ctrl Timeout in
parameter 5-60 Terminal 27 Pulse Output
Variable and a timeout is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0.00 %
[0.00 -
Set the output frequency transferred to
*
100.00 %]
output terminal 29 when the terminal is
configured as [45] Bus Controlled in
parameter 5-63 Terminal 29 Pulse Output
Variable.
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %
[0.00 -
Set the output frequency transferred to
*
100.00 %]
output terminal 29 when the terminal is
configured as [48] Bus Ctrl Timeout in
parameter 5-63 Terminal 29 Pulse Output
Variable and a timeout is detected.
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
[0 -
Set the output frequency transferred to
*
100 %]
output terminal X30/6 when the terminal is
configured as [45] Bus ctrl. in
parameter 5-66 Terminal X30/6 Pulse Output
Variable.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
[0 -
Set the output frequency transferred to output
*
100 %]
terminal X30/6 when the terminal is configured
as [48] Bus Ctrl Timeout in
parameter 5-66 Terminal X30/6 Pulse Output
Variable and a timeout is detected.
MG33MO02
Programming Guide
Danfoss A/S © 01/2018 All rights reserved.
3
3
111