Troubleshooting
A trip is the action following an alarm. The trip coasts the motor and is reset by pressing [Reset] or by a digital input
(parameter group 5-1* Digital Inputs). The original event that caused an alarm cannot damage the frequency converter or
cause dangerous conditions. A trip lock is an action when an alarm occurs, which could damage the frequency converter or
connected parts. A trip lock situation can only be reset by cycling power.
Warning
Alarm
Trip locked
Table 6.2 Indicator Light
Bit Hex
Dec
Alarm word
Alarm Word Extended Status Word
0
00000001
1
Brake check (A28)
1
00000002
2
Pwr.card temp
(A69)
2
00000004
4
Earth fault (A14)
3
00000008
8
Ctrl.card temp
(A65)
4
00000010
16
Ctrl. word TO (A17) Servicetrip,
5
00000020
32
Overcurrent (A13)
6
00000040
64
Torque limit (A12)
7
00000080
128
Motor th over
(A11)
8
00000100
256
Motor ETR over
(A10)
9
00000200
512
Inverter overld.
(A9)
10 00000400
1024
DC under volt (A8) Start failed
11 00000800
2048
DC over volt (A7)
12 00001000
4096
Short circuit (A16)
13 00002000
8192
Inrush fault (A33)
14 00004000
16384
Mains ph. loss (A4) No safety option Mains ph. loss
MG33MO02
Programming Guide
Alarm word 2
Warning word
Servicetrip, read/
Brake check (W28) Start delayed Ramping
write
Servicetrip,
Pwr.card temp
(reserved)
(A69)
Servicetrip,
Earth fault (W14)
typecode/
sparepart
Servicetrip,
Ctrl.card temp
(reserved)
(W65)
Ctrl. word TO
(reserved)
(W17)
Reserved
Overcurrent (W13) Reserved
Reserved
Torque limit (W12) Reserved
Reserved
Motor th over
(W11)
Reserved
Motor ETR over
(W10)
Discharge high
Inverter Overld
(W9)
DC under volt
(W8)
Speed limit
DC over volt (W7)
External interlock DC voltage low
(W6)
Illegal option
DC voltage high
combi.
(W5)
(W4)
Danfoss A/S © 01/2018 All rights reserved.
Yellow
Flashing red
Yellow and red
Warning
Extended
word 2
status word
Stop delayed AMA running
Reserved
Start CW/CCW
start_possible is active, when the
DI selections [12] OR [13] are
active and the requested direction
matches the reference sign
Reserved
Slow down
slow down command active, for
example via CTW bit 11 or DI
Catch up
catch up command active, for
example via CTW bit 12 or DI
Feedback high
feedback >parameter 4-57 Warning
Feedback High
Feedback low
feedback <parameter 4-56 Warning
Feedback Low
Reserved
Output current high
current >parameter 4-51 Warning
Current High
Reserved
Output current low
current <parameter 4-50 Warning
Current Low
Discharge
Output freq high
high
speed >parameter 4-53 Warning
Speed High
Multi-motor
Output freq low
underload
speed <parameter 4-52 Warning
Speed Low
Multi-motor
Brake check OK
overload
brake test NOT OK
Compressor
Braking max.
interlock
BrakePower > Brakepowerlimit
(2-12)
Mechanical
Braking
brake sliding
Safe option
Out of speed range
warning
6
6
281