Parameter Description

3.14 Parameters 15-** Drive Information

Parameter group containing frequency converter
information such as operating data, hardware configu-
ration, and software versions.
3.14.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
[0 - 2147483647 h] View how many hours the frequency
*
converter has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor has run.
*
2147483647 h]
Reset the counter in
parameter 15-07 Reset Running Hours
Counter. The value is saved when the
frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
[0 -
Register the power consumption of
*
2147483647
the motor as an average value over 1
kWh]
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 - 2147483647 ] View the number of times the frequency
*
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
temperature faults.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
overvoltages.
15-06 Reset kWh Counter
Option:
Function:
[0]
Do not reset
No reset of the kWh counter is required.
*
[1]
Reset counter Press [OK] to reset the kWh counter to 0
(see parameter 15-02 kWh Counter).
MG20OB02
Programming Guide
15-07 Reset Running Hours Counter
Option:
[0]
Do not
*
reset
[1]
Reset
counter
15-08 Number of Starts
Range:
0
[0 -
*
2147483647 ]
3.14.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
[0]
*
[1472]
[1473]
[1474]
[1600]
[1601]
[1602]
[1603]
[1610]
[1611]
[1612]
[1613]
[1614]
[1616]
[1617]
[1618]
[1622]
[1625]
[1630]
Danfoss A/S © 05/2018 All rights reserved.
Function:
No reset of the running hours counter is
required.
Select [1] Reset counter and press [OK] to reset
the running hours counter
(parameter 15-01 Running Hours) and
parameter 15-08 Number of Starts to 0 (see
also parameter 15-01 Running Hours).
Function:
NOTICE
This parameter is reset when resetting
parameter 15-07 Reset Running Hours
Counter.
This is a readout parameter only. The
counter shows the number of starts and
stops caused by a normal start/stop
command and/or when entering/leaving
sleep mode.
None
VLT Alarm Word
VLT Warning Word
VLT Ext. Status Word
Control Word
Reference [Unit]
Reference %
Status Word
Power [kW]
Power [hp]
Motor Voltage
Frequency
Motor Current
Torque [Nm]
Speed [RPM]
Motor Thermal
Torque [%]
Torque [Nm] High
DC Link Voltage
3
3
Function:
141

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents

Save PDF