Parameter Descriptions
3.1.4 0-4* LCP Keypad
Enable, disable, and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled
No effect when [Hand On] is pressed. Select [0]
Disabled to avoid accidental start of the
frequency converter in hand-on mode.
[1]
Enabled
The LCP switches to hand-on mode directly
*
when [Hand On] is pressed.
[2]
Password After pressing [Hand On] a password is required.
If parameter 0-40 [Hand on] Key on LCP is
included in My Personal Menu, define the
password in parameter 0-65 Quick Menu
Password. Otherwise define the password in
parameter 0-60 Main Menu Password.
0-41 [Off] Key on LCP
Option:
Function:
[0]
Disabled
Avoids accidental stop of the frequency
converter.
[1]
Enabled
*
[2]
Password Avoids unauthorized stop. If parameter 0-41 [Off]
Key on LCP is included in the Quick Menu, then
define the password in parameter 0-65 Quick
Menu Password.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled
Avoids accidental start of the frequency
converter in auto-on mode.
[1]
Enabled
*
[2]
Password Avoids unauthorized start in auto-on mode. If
parameter 0-42 [Auto on] Key on LCP is included
in the Quick Menu, then define the password in
parameter 0-65 Quick Menu Password.
0-43 [Reset] Key on LCP
Option:
Function:
[0]
Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
Enabled
*
[2]
Password Avoids unauthorized resetting. If
parameter 0-43 [Reset] Key on LCP is included in
the Quick Menu, then define the password in
parameter 0-65 Quick Menu Password.
0-44 [Off/Reset] Key on LCP
Enable or disable the [Off/Reset] key.
Option:
[0]
Disabled
[1]
Enabled
*
MG33MO02
Programming Guide
0-44 [Off/Reset] Key on LCP
Enable or disable the [Off/Reset] key.
Option:
[2]
0-45 [Drive Bypass] Key on LCP
Press [Off] and select [0] Disabled to avoid unintended stop of
the frequency converter. Press [Off] and select [2] Password to
avoid unauthorized bypass of the frequency converter. If
parameter 0-45 [Drive Bypass] Key on LCP is included in the Quick
Menu, define the password in parameter 0-65 Personal Menu
Password.
Option:
[0]
[1]
[2]
3.1.5 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option:
[0]
[1]
[2]
[3]
[4]
[5]
Function:
Danfoss A/S © 01/2018 All rights reserved.
Password
Disabled
Enabled
*
Password
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
No copy
*
All to LCP
Copies all parameters in all set-ups from
the frequency converter memory to the
LCP memory.
All from LCP
Copies all parameters in all set-ups from
the LCP memory to the frequency
converter memory.
Size indep.
Copy only the parameters that are
from LCP
independent of the motor size. The latter
selection can be used to program several
frequency converters with the same
function without disturbing motor data.
File from MCO
to LCP
File from LCP
to MCO
Function:
3
Function:
Select to disable the
key.
31