Section 15
Basic IED functions
15.2
15.2.1
15.2.2
15.2.3
626
Table 501:
Time synchronization PTP: IEC/IEEE 61850-9-3
Supported types of clock
Accuracy
Number of nodes
Ports supported

Parameter setting groups

Functionality
Use the six different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly
adaptable IED that can be applied to a variety of power system scenarios.
Function block
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
SETCHGD
REMSETEN
IEC05000433-3-en.vsd
IEC05000433 V3 EN-US
Figure 279:
ActiveGroup function block
Signals
Table 502:
ACTVGRP Input signals
Name
Type
ACTGRP1
BOOLEAN
ACTGRP2
BOOLEAN
ACTGRP3
BOOLEAN
ACTGRP4
BOOLEAN
ACTGRP5
BOOLEAN
ACTGRP6
BOOLEAN
Boundary Clock (BC), Ordinary Clock (OC),
Transparent Clock (TC)
According to standard IEC/IEEE 61850-9-3
According to standard IEC/IEEE 61850-9-3
All rear Ethernet ports
Default
Description
0
Selects setting group 1 as active
0
Selects setting group 2 as active
0
Selects setting group 3 as active
0
Selects setting group 4 as active
0
Selects setting group 5 as active
0
Selects setting group 6 as active
1MRK 511 424-UEN B
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2
IP1745-1 v1
M12006-6 v7
IP9661-1 v1
M12010-3 v3
IP14073-1 v2
PID-6558-INPUTSIGNALS v6
Bay control REC650 2.2 IEC
Technical manual