Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
13.3.7.5
Table 394:
GOOSEDPRCV Non group settings (basic)
Name
Operation
13.3.7.6
496
Table 392:
GOOSEDPRCV Input signals
Name
BLOCK
SRCDPOUT
Table 393:
GOOSEDPRCV Output signals
Name
DPOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and
communication error
Table continues on next page
Type
Default
Description
BOOLEAN
0
Block of function
INTEGER
0
Source to double point output
Type
Description
INTEGER
Double point output
BOOLEAN
Data valid for double point output
BOOLEAN
Communication valid for double point output
BOOLEAN
Test output
Step
Default
-
Off
Data Value
Updated
0
0
0
0
0
0
1MRK 511 424-UEN B
Description
Operation Off/On
GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4
Data Valid
Comm Valid
1
1
0
1
0
1
0
1
0
1
0
1
0
0
Bay control REC650 2.2 IEC
Technical manual
PID-6828-INPUTSIGNALS v3
PID-6828-OUTPUTSIGNALS v3
PID-6828-SETTINGS v3
Test
0
0
0
1
1
0
0