ABB Relion 650 Series Technical Manual page 147

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
block (B16I). Integers supplied shall be 1=Off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input will mean that the setting is done from Parameter Setting tool.
The active position can be read on outputs MODEAEN resp MODEMEN. The
modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
SESRSYN function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
manEnergOpenBays
TSTENERG
BLKENERG
BLOCK
selectedFuseOK
UHighBusEnerg
DLLB
ULowLineEnerg
BOTH
ManEnerg
ULowBusEnerg
DBLL
UHighLineEnerg
ManEnergDBDL
UMaxEnerg
fBus and fLine ±5 Hz
IEC14000031 V1 EN-US
Figure 56:
Manual energizing
OR
AND
OR
AND
AND
AND
Section 8
Control
MANENOK
OR
tManEnerg
t
OR
AND
TSTENOK
AND
IEC14000031-1-en.vsd
141