Bay control REC650 2.2 IEC
Technical manual
The stated operate time for functions include the operating time for
the binary inputs and outputs.

Binary output modules (BOM)

Introduction
The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.
Design
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 296.
This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section
outputs
SMBO".
Output module
xx00000299.vsd
IEC00000299 V1 EN-US
Figure 296:
Relay pair example
1 Output connection from relay 1
2 Output signal power source connection
3 Output connection from relay 2
1
2
3
Section 16
IED hardware
IP14536-1 v1
"Signal matrix for binary