Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Control
8.3.6.4
Table 104:
SCSWI Non group settings (basic)
Name
CtlModel
PosDependent
tSelect
tResResponse
tSynchrocheck
tSynchronizing
tExecutionFB
tPoleDiscord
SuppressMidPos
InterlockChk
8.3.6.5
.
222
with no priority. If the control model used is Select before operate,
Also the corresponding enable input must be set, and no
interlocking is active. The L_SEL input must be set before
L_OPEN or L_CLOSE is operated, if the control model is Select
before operate.
If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI
are used for a two- or three-phase system, two or more of the inputs
XPOSL1, XPOSL2 and XPOSL3 are connected to the same source.

Settings

Values (Range)
Unit
Dir Norm
-
SBO Enh
Always permitted
-
Not perm at 00/11
0.00 - 600.00
s
0.000 - 60.000
s
0.00 - 600.00
s
0.00 - 600.00
s
0.00 - 600.00
s
0.000 - 60.000
s
Off
-
On
Sel & Op phase
-
Op phase
Operation principle
The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation are
fulfilled. The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.
Control handling
Step
Default
-
SBO Enh
-
Always permitted
0.01
30.00
0.001
5.000
0.01
10.00
0.01
0.00
0.01
30.00
0.001
2.000
-
On
-
Sel & Op phase
1MRK 511 424-UEN B
Description
Specifies control model type
Permission to operate depending on the
position
Maximum time between select and
execute signals
Allowed time from reservation request to
reservation granted
Allowed time for synchrocheck to fulfil
close conditions
Supervision time to get the signal
synchronizing in progress
Maximum time from command execution
to termination
Allowed time to have discrepancy
between the poles
Mid-position is suppressed during time
tIntermediate; tIntermediate is set on
each connected XCBR/XSWI function
individually
Selection if interlock check should be
done in select phase
Bay control REC650 2.2 IEC
Technical manual
PID-6798-SETTINGS v4
M13484-4 v4
M13484-6 v7