Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
10.3.5
Table 318:
SSIML Group settings (basic)
Name
Values (Range)
Operation
LevelAlmLimit
LevelLOLimit
TempAlarmLimit
TempLOLimit
tLevelAlarm
tLevelLockOut
tTempAlarm
Table continues on next page
Bay control REC650 2.2 IEC
Technical manual
Table 316:
SSIML Input signals
Name
BLOCK
BLKALM
SENLEVEL
SENTEMP
SENLVLALM
SENLVLLO
SETLLO
SETTLO
RESETLO
Table 317:
SSIML Output signals
Name
LOCKOUT
LVLLO
TEMPLO
ALARM
LVLALM
TEMPALM
LEVEL
TEMP

Settings

Unit
Off
-
On
1.00 - 100.00
-
1.00 - 100.00
-
-40.00 - 200.00
-
-40.00 - 200.00
-
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
Type
Default
Description
BOOLEAN
0
Block of function
BOOLEAN
0
Block all the alarms
REAL
0.0
Level input from CB
REAL
0.0
Temperature of the insulation medium from CB
BOOLEAN
0
Level alarm signal
BOOLEAN
0
Level lockout signal
BOOLEAN
0
Set level lockout
BOOLEAN
0
Set temperature lockout
BOOLEAN
0
Reset level and temperature lockout
Type
Description
BOOLEAN
Level below lockout level or temperature above
lockout level
BOOLEAN
Level below lockout level
BOOLEAN
Temperature above lockout level
BOOLEAN
Level below alarm level or temperature above
alarm level
BOOLEAN
Level below alarm level
BOOLEAN
Temperature above alarm level
REAL
Level service value
REAL
Temperature of the insulation medium
Step
Default
-
Off
0.01
5.00
0.01
3.00
0.01
30.00
0.01
30.00
0.001
0.000
0.001
0.000
0.001
0.000
Section 10
Monitoring
PID-6951-INPUTSIGNALS v7
PID-6951-OUTPUTSIGNALS v7
Description
Operation Off / On
Alarm setting for level
Level lockout setting
Temperature alarm level setting of the
medium
Temperature lockout level of the medium
Time delay for level alarm
Time delay for level lockout indication
Time delay for temperature alarm
PID-6951-SETTINGS v7