Section 8
Control
8.9.5
Table 142:
SINGLECMD Non group settings (basic)
Name
Operation
8.9.6
270
Settings
Values (Range)
Unit
Off
-
Steady
Pulsed
Operation principle
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of
13 characters in PCM600.
The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
Step
Default
-
Off
1MRK 511 424-UEN B
Description
Operation Off / On
Bay control REC650 2.2 IEC
Technical manual
PID-6189-SETTINGS v6
M12447-3 v3