Section 3
Analog inputs
Name
VTsec10
VTprim10
VTsec11
VTprim11
VTsec12
VTprim12
Table 13:
TRM_10I_2U Non group settings (basic)
Name
CTStarPoint1
CTsec1
CTprim1
CTStarPoint2
CTsec2
CTprim2
CTStarPoint3
CTsec3
CTprim3
CTStarPoint4
CTsec4
CTprim4
CTStarPoint5
CTsec5
CTprim5
CTStarPoint6
CTsec6
CTprim6
CTStarPoint7
CTsec7
CTprim7
CTStarPoint8
CTsec8
CTprim8
Table continues on next page
52
Values (Range)
Unit
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
Values (Range)
Unit
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
Step
Default
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
Step
Default
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
1MRK 511 424-UEN B
Description
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Bay control REC650 2.2 IEC
Technical manual
PID-6598-SETTINGS v6