Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.3.11.4
Table 406:
GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Operation
13.3.11.5
Bay control REC650 2.2 IEC
Technical manual
Name
APP15VAL
COMMVALID
TEST

Settings

Unit
Off
-
On
Operation principle
The APPxVAL output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and
communication error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
At least one of the inputs of this GOOSE block must be linked
either in SMT by means of a cross or in ACT by means of a
GOOSE connection (if easy GOOSE engineering is enabled) to
receive any data. Only those outputs whose source input is linked/
connected will be updated.
Type
Description
BOOLEAN
Apparatus 15 position is valid
BOOLEAN
Communication Valid
BOOLEAN
Test Output
Step
Default
-
Off
Data Value
Updated
0
0
0
0
0
0
Updated
Updated
0
Section 13
Station communication
Description
Operation Off/On
GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1
Data Valid
Comm Valid
1
1
0
1
0
1
0
1
0
1
0
1
0
0
1
1
1
1
0
0
SEMOD173168-1 v2
PID-6831-SETTINGS v3
Test
0
0
0
1
1
0
0
0
1
0
507