ABB Relion 650 Series Technical Manual page 349

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
tWarning
tAlarm
BLOCK
RESET
IN
IEC12000195 V4 EN-US
Figure 167:
TEIGAPC Simplified logic
TEIGAPC main functionalities
integration of the elapsed time when IN has been high
applicable to long time integration (≤999 999.9 seconds)
output ACCTIME presents integrated value in seconds
integrated value is retained in nonvolatile memory
any retained value with a warning/alarm/overflow is used as initiation
value for the integration following by a restart
RESET: Reset of the integration value. Consequently all other outputs are also
reset
unconditionally on the input IN value
reset the value of the nonvolatile memory to zero
BLOCK: Freeze the integration and block/reset the other outputs
unconditionally on the signal value
BLOCK request overrides RESET request
Monitor and report the conditions of limit transgression
overflow if output ACCTIME >999999.9 seconds
alarm if ACCTIME > tAlarm
warning if ACCTIME > tWarning
The ACCTIME output represents the integrated time in seconds while tOverflow,
tAlarm and tWarning are the time limit parameters in seconds.
tAlarm and tWarning are user settable limits. They are also independent, that is,
there is no check if tAlarm > tWarning.
Loop Delay
Transgression Supervision
Time Integration
Loop Delay
Section 9
OVERFLOW
WARNING
Plus Retain
IEC12000195-4-en.vsd
Logic
ALARM
ACCTIME