Section 8
Control
8.3.5.3
Table 101:
LOCREM Non group settings (basic)
Name
ControlMode
8.3.5.4
218
Name
HMICTR4
HMICTR5
HMICTR6
HMICTR7
HMICTR8
HMICTR9
HMICTR10
HMICTR11
HMICTR12

Settings

Values (Range)
Unit
Internal LR-switch
-
External LR-switch
Operation principle
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in Figure 89, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
used. When the local HMI is used, the inputs are not used. The switching between
external and local HMI source is done through the parameter ControlMode. The
outputs from the LOCREM function block control the output PSTO (Permitted
Source To Operate) on Bay control (QCBAY).
Type
Description
INTEGER
Bitmask output 4 to local remote LHMI input
INTEGER
Bitmask output 5 to local remote LHMI input
INTEGER
Bitmask output 6 to local remote LHMI input
INTEGER
Bitmask output 7 to local remote LHMI input
INTEGER
Bitmask output 8 to local remote LHMI input
INTEGER
Bitmask output 9 to local remote LHMI input
INTEGER
Bitmask output 10 to local remote LHMI input
INTEGER
Bitmask output 11 to local remote LHMI input
INTEGER
Bitmask output 12 to local remote LHMI input
Step
Default
-
Internal LR-switch
1MRK 511 424-UEN B
Description
Control mode for internal/external LR-
switch
Bay control REC650 2.2 IEC
Technical manual
PID-3944-SETTINGS v7
PID-3943-SETTINGS v2