Pulse Timer Function Block Pulsetimer - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
9.7.6
9.7.6.1
9.7.6.2
9.7.6.3
Table 185:
PULSETIMER Non group settings (basic)
Name
Values (Range)
t
9.7.6.4
Bay control REC650 2.2 IEC
Technical manual

Pulse timer function block PULSETIMER

The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting the operation time of outputs. The PULSETIMER has a settable length.
When the input is 1, the output will be 1 for the time set by the time delay
parameter t. Then it returns to 0.
Function block
PULSETIMER
INPUT
IEC04000407-3-en.vsd
IEC04000407 V3 EN-US
Figure 143:
PULSETIMER function block
Signals
Table 183:
PULSETIMER Input signals
Name
INPUT
Table 184:
PULSETIMER Output signals
Name
OUT
Settings
Unit
0.000 - 90000.000
s
Technical data
Table 186:
Number of PULSETIMER instances
Logic block
PULSETIMER
OUT
Type
Default
Description
BOOLEAN
0
Input to pulse timer
Type
Description
BOOLEAN
Output from pulse timer
Step
Default
0.001
0.010
Quantity with cycle time
Range or Value
3 ms
8 ms
100 ms
10
10
20
(0.000–90000.000) s
Section 9
PID-6985-INPUTSIGNALS v1
PID-6985-OUTPUTSIGNALS v1
Description
Time delay of function
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2
Accuracy
±0.5% ±10 ms
Logic
IP11016-1 v2
M11466-3 v3
M11465-3 v4
PID-6985-SETTINGS v1
305