Monitored Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Logic
9.16.6
9.16.7
346

Monitored data

Table 269:
INTCOMP Monitored data
Name
Type
INEQUAL
BOOLEAN
INHIGH
BOOLEAN
INLOW
BOOLEAN
Operation principle
The comparison can be done in two ways,
Between 2 inputs, INPUT and REF
Between INPUT and the value set by the user SetValue.
The selection of reference value for comparison can be done through setting
RefSource. If RefSource is selected as Input REF then the reference value for
comparison is taken from second input signal (REF). If RefSource is selected as Set
Value then the reference value for comparison is taken from setting (SetValue).
The comparison can be done either between absolute values or signed values and it
depends on the setting EnaAbs. If EnaAbs is selected as Absolute then both input
and reference value is converted into absolute values and comparison is done. If
EnaAbs is selected as Signed then the comparison is done without any conversion.
The function has three state outputs high, low and equal to condition. It will check
the following condition and give corresponding outputs.
If the input is above the reference value then INHIGH is set HIGH
If the input is below the reference value then INLOW is set HIGH
If the input is equal to reference value then INEQUAL is set HIGH
Values (Range)
Unit
-
-
-
-
-
-
1MRK 511 424-UEN B
PID-6928-MONITOREDDATA v1
Description
Input value is equal to
the reference value
Input value is higher
than the reference value
Input value is lower than
the reference value
GUID-E9C1B863-ACA7-45C0-91F1-A51FE38755FE v2
Bay control REC650 2.2 IEC
Technical manual