1MRK 511 424-UEN B
9.1.5
Table 145:
SMPPTRC Group settings (basic)
Name
Values (Range)
Operation
Program
tTripMin
tWaitForPHS
Table 146:
SMPPTRC Group settings (advanced)
Name
Values (Range)
TripLockout
AutoLock
tEvolvingFault
Bay control REC650 2.2 IEC
Technical manual
Table 144:
SMPPTRC Output signals
Name
TRIP
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
STN
FW
REV

Settings

Unit
Off
-
On
3 phase
-
1ph/3ph
1ph/2ph/3ph
0.000 - 60.000
s
0.020 - 0.500
s
Unit
Off
-
On
Off
-
On
0.000 - 60.000
s
Type
Description
BOOLEAN
General trip output signal
BOOLEAN
Trip signal from phase L1
BOOLEAN
Trip signal from phase L2
BOOLEAN
Trip signal from phase L3
BOOLEAN
Trip single-pole
BOOLEAN
Trip two-pole
BOOLEAN
Trip three-pole
BOOLEAN
Circuit breaker lockout output (set until reset)
BOOLEAN
General start signal
BOOLEAN
Start signal from phase L1
BOOLEAN
Start signal from phase L2
BOOLEAN
Start signal from phase L3
BOOLEAN
Start signal from neutral
BOOLEAN
General forward signal
BOOLEAN
General reverse signal
Step
Default
-
Off
-
1ph/3ph
0.001
0.150
0.001
0.050
Step
Default
-
Off
-
Off
0.001
2.000
Section 9
GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1
GUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1
Description
Operation Off / On
Three ph; single or three ph; single, two
or three ph trip
Minimum duration of trip output signal
Secure 3-pole trip when phase selection
failed
Description
Latch TRIP output when SETLKOUT
input is activated
Activate CLLKOUT output when TRIP
output is activated
Secure 3-pole tripping at evolving faults
Logic