Section 9
Logic
9.8.10.1
9.8.10.2
9.8.10.3
Table 239:
TIMERSETQT Group settings (basic)
Name
Operation
t
9.8.10.4
324
The Settable timer function block (TIMERSETQT) has two outputs for delay of the
input signal at pick-up and drop-out. The timer has a settable time delay (t). It also
has an Operation setting On/Off that controls the operation of the timer.
When the output changes value, the timestamp of the output signal is updated. The
supported "quality" state bits are propagated from the input to the output at each
execution cycle. A change of these bits will not lead to an updated timestamp on
the output.
TIMERSETQT can propagate the quality, value and the timestamps of the signals
via IEC 61850.

Function block

TIMERSETQT
INPUT
IEC14000068-1-en.vsd
IEC14000068 V1 EN-US
Figure 158:
TIMERSETQT function
Signals
Table 237:
TIMERSETQT Input signals
Name
INPUT
Table 238:
TIMERSETQT Output signals
Name
ON
OFF
Settings
Values (Range)
Unit
Off
-
On
0.000 - 90000.000
s
Technical data
ON
OFF
Type
Default
Description
BOOLEAN
0
Input signal
Type
Description
BOOLEAN
Output signal, pick-up delayed
BOOLEAN
Output signal, drop-out delayed
Step
Default
-
Off
0.001
0.000
1MRK 511 424-UEN B
GUID-3830BCA7-4876-481E-B5AC-2104675232E7 v5
GUID-13589BAE-38AE-46A1-8E9F-94BCD1CBCBF1 v1
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3816-INPUTSIGNALS v5
PID-3816-OUTPUTSIGNALS v5
Description
Operation Off/On
Delay for settable timer n
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
Bay control REC650 2.2 IEC
Technical manual
PID-3816-SETTINGS v5