Section 10
Monitoring
Table 291:
VMMXU Non group settings (basic)
Name
UL12DbRepInt
Operation
UL12ZeroDb
UL12Min
UL12Max
UL12RepTyp
GlobalBaseSel
UL12AngDbRepInt
UL23DbRepInt
UL23ZeroDb
UL23Min
UL23Max
UL23RepTyp
UL23AngDbRepInt
UL31DbRepInt
UL31ZeroDb
UL31Min
UL31Max
UL31RepTyp
UL31AngDbRepInt
364
Values (Range)
Unit
1 - 100000
Type
Off
-
On
0 - 100000
m%
0.0 - 200.0
%UB
0.0 - 200.0
%UB
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 12
-
1 - 100000
s
1 - 100000
Type
0 - 100000
m%
0.0 - 200.0
%UB
0.0 - 200.0
%UB
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 100000
s
1 - 100000
Type
0 - 100000
m%
0.0 - 200.0
%UB
0.0 - 200.0
%UB
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 100000
s
Step
Default
1
10
-
Off
500
1000
0.1
50.0
0.1
200.0
-
Cyclic
1
1
1
10
1
10
500
1000
0.1
50.0
0.1
200.0
-
Cyclic
1
10
1
10
500
1000
0.1
50.0
0.1
200.0
-
Cyclic
1
10
1MRK 511 424-UEN B
Description
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Mode On / Off
Magnitude zero point clamping in
0,001% of range
Minimum value in % of UBase
Maximum value in % of UBase
Reporting type
Selection of one of the Global Base
Value groups
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Magnitude zero point clamping in
0,001% of range
Minimum value in % of UBase
Maximum value in % of UBase
Reporting type
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Magnitude zero point clamping in
0,001% of range
Minimum value in % of UBase
Maximum value in % of UBase
Reporting type
Cyclic report interval (s)
Bay control REC650 2.2 IEC
Technical manual
PID-6738-SETTINGS v2