ABB Relion 650 Series Technical Manual page 701

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
Table 568:
Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
Table 569:
Environmental tests
Test
Cold operation test
Cold storage test
Dry heat operation test
Dry heat storage test
Change of temperature test
Damp heat test, steady state
Damp heat test, cyclic
Table 570:
CE compliance
Test
Immunity
Emissivity
Low voltage directive
Table 571:
Mechanical tests
Test
Type test values
Vibration response test
Class II
Vibration endurance
Class I
test
Shock response test
Class I
Shock withstand test
Class I
Bump test
Class I
Seismic test
Class II
Type test values
2.0 kV AC, 1 min.
(SFP galvanic RJ45: 1.0
kVrms, 1 min.)
5 kV, 1.2/50ms, 0.5 J
1 kV, 1.2/50 ms 0.5 J, SFP
galvanic RJ45
> 100 MW at 500 VDC
Type test value
Test Ad for 16 h at -25°C
Test Ab for 16 h at -40°C
Test Bd for 16 h at +70°C
Test Bb for 16 h at +85°C
Test Nb for 5 cycles at -25°C
to +70°C
Test Ca for 10 days at
+40°C and humidity 93%
Test Db for 6 cycles at +25
to +55°C and humidity 93 to
95% (1 cycle = 24 hours)
According to
EN 60255–26
EN 60255–26
EN 60255–27
Section 16
IED hardware
Reference standard
IEC 60255-27
ANSI C37.90
IEEE 802.3-2015,
Environment A
Reference standard
IEC 60068-2-1
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-2
IEC 60068-2-14
IEC 60068-2-78
IEC 60068-2-30
Reference standards
IEC 60255-21-1
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-3
695