tAlarm and tWarning are possible to be defined with a resolution of 10 ms,
depending on the level of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs
freeze if an overflow occurs.

Operation accuracy

The accuracy of TEIGAPC depends on essentially three factors
function cycle time
the pulse length
the number of pulses, that is, the number of rising and falling flank pairs
In principle, a shorter function cycle time, longer integrated time length or more
pulses may lead to reduced accuracy.
Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory.
Technical data
Table 264:
TEIGAPC Technical data
Function
Elapsed time
3
integration
8
100
Table 265:
Number of TEIGAPC instances
Function
3 ms
TEIGAPC
4
Comparator for integer inputs INTCOMP
Identification
Function description
Comparison of integer values
Cycle time (ms)
Range or value
0 ~ 999999.9 s
0 ~ 999999.9 s
0 ~ 999999.9 s
Quantity with cycle time
8 ms
4
IEC 61850
identification
INTCOMP
1MRK 511 424-UEN B
GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3
GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4
Accuracy
±0.2% or ±20 ms
whichever is greater
±0.2% or ±100 ms
whichever is greater
±0.2% or ±250 ms
whichever is greater
100 ms
4
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
Int<=>
Bay control REC650 2.2 IEC
Technical manual