Technical Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Logic
9.14.7
9.15
9.15.1
9.15.2
340
Name of OUTx
Type
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx
(1≤x≤16) are active equals 65535. This is the highest integer that can be converted
to boolean by the ITBGAPC function block.
The operator position input (PSTO) determines the operator place. The integer
number that is communicated to the ITBGAPC can only be written to the block
while the PSTO is in position "Remote". If PSTO is in position "Off" or "Local",
then no changes are applied to the outputs.

Technical data

Table 260:
Number of ITBGAPC instances
Function
3 ms
ITBGAPC
4
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
Identification
Function Description
Elapsed time integrator
Functionality
Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the
elapsed time when a given binary signal has been high, see also Figure 165.
Description
Value when
activated
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
Quantity with cycle time
8 ms
4
IEC 61850
IEC 60617
identification
identification
TEIGAPC
-
1MRK 511 424-UEN B
Value when
deactivated
0
0
0
0
0
0
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2
100 ms
8
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
ANSI/IEEE C37.2 device
number
-
GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3
Bay control REC650 2.2 IEC
Technical manual