Generic Communication Function For Measured Value Mvgapc - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.3.6
13.3.6.1
13.3.6.2
13.3.6.3
Bay control REC650 2.2 IEC
Technical manual
Generic communication function for Measured Value
MVGAPC
Functionality
Generic communication function for measured values (MVGAPC) function is used
to send the instantaneous value of an analog signal to other systems or equipment
in the substation. It can also be used inside the same IED, to attach a RANGE
aspect to an analog value and to permit measurement supervision on that value.
Function block
MVGAPC
BLOCK
^VALUE
^IN
RANGE
IEC14000022-1-en.vsd
IEC14000022 V1 EN-US
Figure 236:
MVGAPC function block
Signals
Table 388:
MVGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN
REAL
Table 389:
MVGAPC Output signals
Name
Type
VALUE
REAL
RANGE
INTEGER
Station communication
Default
Description
0
Block of function
0
Analog input value
Description
Magnitude of deadband value
Range
Section 13
SEMOD55402-1 v3
SEMOD55872-5 v10
SEMOD54712-4 v4
SEMOD55948-1 v2
PID-6753-INPUTSIGNALS v1
PID-6753-OUTPUTSIGNALS v1
493