8.3.9.4
Table 113:
XLNPROXY Non group settings (basic)
Name
Values (Range)
SwitchType
tStartMove
tIntermediate
Bay control REC650 2.2 IEC
Technical manual
Name
OPRCVD
OPRCVD_VLD
OPOK
OPOK_VLD
EEHEALTH
EEHEALTH_VLD
OPCAP
OPCAP_VLD
COMMVALID
XIN
Table 112:
XLNPROXY Output signals
Name
XPOS
SELECTED
OP_BLKD
CL_BLKD
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
EEHEALTH
OPCAP

Settings

Unit
Circuit Breaker
-
Load Break
Disconnector
Earthing Switch
HS Earth Switch
0.000 - 60.000
s
0.000 - 60.000
s
Type
Default
Description
BOOLEAN
0
Operate command for a controllable data object
received
BOOLEAN
0
Valid data on OPRCVD input
BOOLEAN
0
Operate command for a controllable data object
accepted
BOOLEAN
0
Valid data on OPOK input
INTEGER
-1
External equipment health
BOOLEAN
0
Valid data on EEHEALTH input
INTEGER
-1
Operating capability
BOOLEAN
0
Valid data on OPCAP input
BOOLEAN
0
Communication valid
GROUP
-
Execution information from CSWI
SIGNAL
Type
Description
GROUP SIGNAL
Group connection to CSWI
BOOLEAN
Select conditions are fulfilled
BOOLEAN
Indication that the function is blocked for open
commands
BOOLEAN
Indication that the function is blocked for close
commands
BOOLEAN
Apparatus open position
BOOLEAN
Apparatus closed position
INTEGER
Operation counter value
INTEGER
Latest value of the error indication during
command
INTEGER
External equipment health. 1=No warning or
alarm, 2=Warning, 3=Alarm
INTEGER
Switch / breaker operating capability
Step
Default
-
Circuit Breaker
0.001
0.100
0.001
0.150
Section 8
PID-6712-OUTPUTSIGNALS v3
Description
0 = CB, 1 = Load Break, 2 =
Disconnector, 3 = Earthing Switch, 4 =
High Speed Earthing Switch
Supervision time for the apparatus to
move after a command
Allowed time for intermediate position
Control
PID-6712-SETTINGS v3
243