ABB Relion 650 Series Technical Manual page 140

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Control
Name
AutoEnerg
ManEnerg
ManEnergDBDL
UHighBusEnerg
UHighLineEnerg
ULowBusEnerg
ULowLineEnerg
UMaxEnerg
tAutoEnerg
tManEnerg
Table 59:
SESRSYN Non group settings (basic)
Name
SelPhaseBus1
GblBaseSelBus
GblBaseSelLine
SelPhaseBus2
Table continues on next page
134
Values (Range)
Unit
Off
-
DLLB
DBLL
Both
Off
-
DLLB
DBLL
Both
Off
-
On
50.0 - 120.0
%UBB
50.0 - 120.0
%UBL
10.0 - 80.0
%UBB
10.0 - 80.0
%UBL
50.0 - 180.0
%UB
0.000 - 60.000
s
0.000 - 60.000
s
Values (Range)
Unit
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
1 - 12
-
1 - 12
-
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Step
Default
-
DLLB
-
Both
-
Off
1.0
80.0
1.0
80.0
1.0
40.0
1.0
40.0
1.0
115.0
0.001
0.100
0.001
0.100
Step
Default
-
Phase L1
1
1
1
1
-
Phase L1
1MRK 511 424-UEN B
Description
Automatic energizing check mode
Manual energizing check mode
Manual dead bus, dead line energizing
Voltage high limit bus for energizing
check in % of UBaseBus
Voltage high limit line for energizing
check in % of UBaseLine
Voltage low limit bus for energizing
check in % of UBaseBus
Voltage low limit line for energizing
check in % of UBaseLine
Maximum voltage for energizing in % of
UBase, Line and/or Bus
Time delay for automatic energizing
check
Time delay for manual energizing check
Description
Select phase for busbar1
Selection of one of the Global Base
Value groups, Bus
Selection of one of the Global Base
Value groups, Line
Select phase for busbar2
Bay control REC650 2.2 IEC