Section 8
Control
8.3.10
8.3.10.1
8.3.10.2
246
It is possible to speed up the command response for when the command has been
started by the switch in the breaker IED by connecting the inputs OPOK and
OPOK_VAL. Then the blocking check is only done until OPOK is activated and
confirmation of that the command has been started is given to the SCSWI function.
If the inputs STSELD and STSELD_V are connected, the switch in the breaker
IED is assumed to use selection. Then the SCSWI will wait for a selected
indication, STSELD input of XLNPROXY, before accepting selection, this
information is transferred to the SCSWI function from the XLNPROXY through
the group connection XPOS. If STSELD is not activated within tSelect of the
SCSWI function, the selection is deemed failed and it gives a negative selection
acknowledgement to the command issuer with the cause Select-failed. Further, if
the communication is lost, or the data received is deemed invalid, the selection will
also fail with cause Select-failed from the SCSWI.

Bay reserve QCRSV

Functionality
The purpose of the reservation (QCRSV) function is primarily to transfer
interlocking information between IEDs in a safe way and to prevent double
operation in a bay, switchyard part, or complete substation.
Function block
QCRSV
EXCH_IN
RES_GRT1
RES_RQ1
RES_GRT2
RES_RQ2
RES_GRT3
RES_RQ3
RES_GRT4
RES_RQ4
RES_GRT5
RES_RQ5
RES_GRT6
RES_RQ6
RES_GRT7
RES_RQ7
RES_GRT8
RES_RQ8
RES_BAYS
BLOCK
ACK_TO_B
OVERRIDE
RESERVED
RES_DATA
EXCH_OUT
IEC05000340-3-en.vsdx
IEC05000340 V3 EN-US
Figure 109:
QCRSV function block
1MRK 511 424-UEN B
IP15629-1 v2
M13506-3 v5
M13509-3 v3
Bay control REC650 2.2 IEC