Technical Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
10.3.8
10.4
10.4.1
Bay control REC650 2.2 IEC
Technical manual
alarm, two time delays tTempAlarm or tTempLockOuthave been included. If the
temperature goes above the settings for more than these time delays, the
corresponding alarm TEMPALM or lockout TEMPLO will be initiated. The
SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input
RESETLO. The binary input BLKALM can be used for blocking the alarms, and
the BLOCK input can block both alarm and the lockout indications.
The output ALARM goes high if the level alarm condition or the temperature
alarm condition exists in the oil insulated devices. The output ALARM can be
blocked by activating BLOCK or BLKALM inputs.
The output LOCKOUT goes high if the pressure lockout condition or the
temperature lockout condition exists in the oil insulated devices and it resets by
using the binary input RESETLO. The output LOCKOUT can be blocked by
activating BLOCK input.

Technical data

Table 320:
SSIMLTechnical data
Function
Oil alarm level
Oil lockout level
Temperature alarm level
Temperature lockout level
Time delay for oil alarm
Reset time delay for oil alarm
Time delay for oil lockout
Time delay for temperature
alarm
Reset time delay for
temperature alarm
Time delay for temperature
lockout
Breaker monitoring SSCBR
Identification
Function description
Breaker monitoring
Range or value
1.00-100.00
1.00-100.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSCBR
-
Section 10
Monitoring
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8
Accuracy
±10.0% of set value
±10.0% of set value
±2.5% of set value
±2.5% of set value
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7
ANSI/IEEE C37.2
device number
-
393

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650