Section 13
Station communication
530
Function block
First LON address in
function block
EVENT:17
1280
EVENT:18
1296
EVENT:19
1312
EVENT:20
1328
Event masks
Event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/IED settings/ Monitoring / Event Function or via
parameter setting tool (PST) as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting
criteria for integers has no semantic, prefer to be set by the user)
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the EVENT function
block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the EVENT function block.
Double indications
Double indications can only be reported for the first 8 inputs on an EVENT
function block.
00 generates an intermediate event with the read status 0
01 generates an open event with the read status 1
10 generates a close event with the read status 2
11 generates an undefined event with the read status 3
Analog value
All analog values are reported cyclic. The reporting interval is taken from the
connected function if there is a limit supervised signal. Otherwise it is taken from
the EVENT function block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent
SPA-bus message is an explicit LON message which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
1MRK 511 424-UEN B
M15083-78 v4
M15083-123 v3
M15083-126 v3
M15083-135 v4
M15083-80 v4
Bay control REC650 2.2 IEC
Technical manual