16 binary inputs. LON enables these to be transmitted to the equivalent receiving
function block, MULTICMDRCV, which has 16 binary outputs.

Design

General
The common behavior for all 16 outputs of the MULTICMDRCV is set to either of
two modes: Steady or Pulse.
1 = Steady: This mode simply forwards the received signals to the binary
outputs.
2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse
with a duration of exactly one execution cycle is triggered on the
corresponding binary output. This means that no connected function block
may have a cycle time that is higher than the execution cycle time of the
particular MULTICMDRCV instance.
Function block
MULTICMDRCV
BLOCK
ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
IEC06000007-2-en.vsd
IEC06000007 V2 EN-US
Figure 268:
MULTICMDRCV function block
Section 13
Station communication
SEMOD119958-1 v1
M14792-3 v3
SEMOD119978-1 v1
SEMOD119976-5 v2
587