Table 575:
ANSI Inverse time characteristics for Sensitive directional residual overcurrent and
power protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
×
t
B k
(
)
ç
÷
-
P
I
1
è
ø
EQUATION1249-SMALL V3 EN-US
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN-US
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
Inverse time characteristics
Range or value
0.05 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0 ,
tr=29.1
A=19.61, B=0.491, P=2.0 ,
tr=21.6
A=0.0086, B=0.0185, P=0.02,
tr=0.46
A=0.0515, B=0.1140, P=0.02,
tr=4.85
A=64.07, B=0.250, P=2.0,
tr=30
A=28.55, B=0.712, P=2.0,
tr=13.46
A=0.086, B=0.185, P=0.02,
tr=4.6
Section 19
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4
Accuracy
ANSI/IEEE C37.112 ,
±5.0% or ±160 ms
whichever is greater