Functionality - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Monitoring
10.4.2
10.4.3
10.4.4
394

Functionality

Function block
SSCBR
I3P*
OPENPOS
BLOCK
CLOSEPOS
BLKALM
INVDPOS
TRIND
TRCMD
POSOPEN
TRVTOPAL
POSCLOSE
TRVTCLAL
PRESALM
OPERALM
PRESLO
OPERLO
SPRCHRST
CBLIFEAL
SPRCHRD
MONALM
RSTCBWR
IPOWALPH
RSTTRVT
IPOWLOPH
RSTIPOW
SPCHALM
RSTSPCHT
GPRESALM
GPRESLO
IEC13000231-2-en.vsd
IEC13000231 V2 EN-US
Figure 186:
SSCBR function block
Signals
Table 321:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKALM
BOOLEAN
TRIND
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
PRESALM
BOOLEAN
PRESLO
BOOLEAN
SPRCHRST
BOOLEAN
SPRCHRD
BOOLEAN
RSTCBWR
BOOLEAN
RSTTRVT
BOOLEAN
RSTIPOW
BOOLEAN
RSTSPCHT
BOOLEAN
Default
Description
-
Group signal for current input
0
Block all the alarm and lockout indication
0
Block all the alarms
0
Trip command from trip circuit
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Pressure alarm indication from CB
0
Pressure lockout indication from CB
0
CB spring charging started indication signal
0
CB spring charged indication signal
0
Reset of CB remaining life and operation counter
0
Reset of CB closing and opening travel times
0
Reset of accumulated I^CurrExponent
0
Reset of CB spring charging time
1MRK 511 424-UEN B
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v13
GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11
PID-3267-INPUTSIGNALS v10
Bay control REC650 2.2 IEC
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650