Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
8.1.5
Table 58:
SESRSYN Group settings (basic)
Name
Values (Range)
Operation
OperationSynch
UHighBusSynch
UHighLineSynch
UDiffSynch
FreqDiffMin
FreqDiffMax
CloseAngleMax
FreqRateChange
tBreaker
tClosePulse
tMaxSynch
tMinSynch
OperationSC
UHighBusSC
UHighLineSC
UDiffSC
FreqDiffA
FreqDiffM
PhaseDiffA
PhaseDiffM
tSCA
tSCM
Table continues on next page
Bay control REC650 2.2 IEC
Technical manual

Settings

Unit
Off
-
On
Off
-
On
50.0 - 120.0
%UBB
50.0 - 120.0
%UBL
0.02 - 0.50
pu
0.003 - 0.250
Hz
0.050 - 1.000
Hz
15.0 - 30.0
Deg
0.000 - 0.500
Hz/s
0.000 - 1.000
s
0.050 - 60.000
s
0.00 - 6000.00
s
0.000 - 60.000
s
Off
-
On
50.0 - 120.0
%UBB
50.0 - 120.0
%UBL
0.02 - 0.50
pu
0.003 - 1.000
Hz
0.003 - 1.000
Hz
5.0 - 90.0
Deg
5.0 - 90.0
Deg
0.000 - 60.000
s
0.000 - 60.000
s
Step
Default
-
Off
-
Off
1.0
80.0
1.0
80.0
0.01
0.10
0.001
0.010
0.001
0.200
1.0
15.0
0.001
0.300
0.001
0.080
0.001
0.200
0.01
600.00
0.001
2.000
-
On
1.0
80.0
1.0
80.0
0.01
0.15
0.001
0.010
0.001
0.010
1.0
25.0
1.0
25.0
0.001
0.100
0.001
0.100
Section 8
Description
Operation Off / On
Operation for synchronizing function
Off/On
Voltage high limit bus for synchronizing
in % of UBaseBus
Voltage high limit line for synchronizing
in % of UBaseLine
Voltage difference limit for synchronizing
in p.u of set voltage base value
Minimum frequency difference limit for
synchronizing
Maximum frequency difference limit for
synchronizing
Maximum closing angle between bus
and line for synchronizing
Maximum allowed frequency rate of
change
Closing time of the breaker
Breaker closing pulse duration
Resets synch if no close has been made
before set time
Minimum time to accept synchronizing
conditions
Operation for synchronism check
function Off/On
Voltage high limit bus for synchrocheck
in % of UBaseBus
Voltage high limit line for synchrocheck
in % of UBaseLine
Voltage difference limit for synchrocheck
in p.u of set voltage base value
Frequency difference limit between bus
and line Auto
Frequency difference limit between bus
and line Manual
Phase angle difference limit between
bus and line Auto
Phase angle difference limit between
bus and line Manual
Time delay output for synchrocheck Auto
Time delay output for synchrocheck
Manual
Control
PID-6724-SETTINGS v2
133