Section 13
Station communication
584
ASDU23
In 'list of recorded disturbances' (ASDU23) an information element named SOF
(status of fault) exists. This information element consists of 4 bits and indicates
whether:
Bit TP: the protection equipment has tripped during the fault
Bit TM: the disturbance data are currently being transmitted
Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
Bit OTEV: the disturbance data recording has been initiated by another event
than start
The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
TP
Recorded fault with trip. [1]
TM
Disturbance data waiting for transmission [0]
OTEV
Disturbance data initiated by other events [1]
Another information element in ASDU23 is the FAN (fault number). According to
the standard this is a number that is incremented when a protection function takes
action. FAN is equal to disturbance number, which is incremented for each
disturbance.
ASDU26 / ASDU31
When a disturbance has been selected by the master by sending ASDU24, the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is just as FAN, equal to disturbance number.
Interoperability, physical layer
Electrical Interface
EIA RS-485
number of loads
Optical interface
glass fiber
plastic fiber
Transmission speed
9600 bit/s
19200 bit/s
Table continues on next page
Supported
Yes
32
Yes
Yes
Yes
Bay control REC650 2.2 IEC
1MRK 511 424-UEN B
M11874-482 v4
Technical manual