Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 8
Control
8.5.5
Table 130:
VSGAPC Non group settings (basic)
Name
Operation
CtlModel
Mode
tSelect
tPulse
8.5.6
260
Name
POS2
CMDPOS12
CMDPOS21

Settings

Values (Range)
Unit
Off
-
On
Dir Norm
-
SBO Enh
Steady
-
Pulsed
0.000 - 60.000
s
0.000 - 60.000
s
Operation principle
Selector mini switch (VSGAPC) function can be used for double purpose, in the
same way as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that a symbol is associated
with a controllable object, otherwise the symbol won't be displayed
on the screen. A symbol is created and configured in GDE tool in
PCM600.
The PSTO input is connected to the Local remote switch to have a selection of
operators place, operation from local HMI (Local) or through IEC 61850 (Remote).
An INTONE connection from Fixed signal function block (FXDSIGN) will allow
operation from local HMI.
Type
Description
BOOLEAN
Position 2 indication, logical signal
BOOLEAN
Execute command from position 1 to position 2
BOOLEAN
Execute command from position 2 to position 1
Step
Default
-
Off
-
Dir Norm
-
Pulsed
0.001
30.000
0.001
0.200
1MRK 511 424-UEN B
Description
Operation Off / On
Specifies the type for control model
according to IEC 61850
Operation mode
Max time between select and execute
signals
Command pulse lenght
Bay control REC650 2.2 IEC
Technical manual
PID-6504-SETTINGS v6
SEMOD158762-4 v7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents