1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
Function
Reactive power, Q
Apparent power, S
Power factor, cos (φ)
Table 306:
CMMXU technical data
Function
Current at symmetrical load
Phase angle at symmetrical load
Table 307:
VMMXU technical data
Function
Voltage
Phase angle
Table 308:
CMSQI technical data
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Range or value
(10 to 300) V
(0.1-4.0) x I
r
(100 to 220) V
(0.5-2.0) x I
r
cos φ< 0.7
(10 to 300) V
(0.1-4.0) x I
r
(100 to 220) V
(0.5-2.0) x I
r
(10 to 300) V
(0.1-4.0) x I
r
(100 to 220) V
(0.5-2.0) x I
r
Range or value
(0.1-4.0) × I
r
(0.1-4.0) × I
r
Range or value
(10 to 300) V
(10 to 300) V
Range or value
(0.1–4.0) × I
r
(0.1–1.0) × I
r
(0.1–1.0) × I
r
(0.1–4.0) × I
r
Section 10
Monitoring
Accuracy
±0.5% of S
at S ≤0.5 x S
r
r
±0.5% of S at S > 0.5 x S
r
±0.2% of Q
±0.5% of S
at S ≤0.5 x S
r
r
±0.5% of S at S >0.5 x S
r
±0.2% of S
<0.02
<0.01
GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6
Accuracy
±0.3% of I
at I ≤ 0.5 × I
r
r
±0.3% of I at I > 0.5 × I
r
±1.0 degrees at 0.1 × I
< I ≤
r
0.5 × I
r
±0.5 degrees at 0.5 × I
< I ≤
r
4.0 × I
r
GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5
Accuracy
±0.3% of I
at I ≤ 0.5 × I
r
r
±0.3% of I at I > 0.5 × I
r
±0.3% of I
at I ≤ 0.5 × I
r
r
±0.3% of I at I > 0.5 × I
r
±0.3% of I
at I ≤ 0.5 × I
r
r
±0.3% of I at I > 0.5 × I
r
±1.0 degrees at 0.1 × I
< I ≤
r
0.5 × I
r
±0.5 degrees at 0.5 × I
< I ≤
r
4.0 × I
r
385