1MRK 511 424-UEN B
7.2.5
Table 52:
FUFSPVC Group settings (basic)
Name
Values (Range)
Operation
OpMode
3U0>
3I0<
3U2>
3I2<
OpDUDI
DU>
DI<
UPh>
IPh>
SealIn
USealln<
IDLD<
UDLD<
Table 53:
FUFSPVC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
Bay control REC650 2.2 IEC
Technical manual

Settings

Unit
Off
-
On
Off
-
UNsINs
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
1 - 100
%UB
1 - 100
%IB
1 - 100
%UB
1 - 100
%IB
Off
-
On
1 - 100
%UB
1 - 100
%IB
1 - 100
%UB
1 - 100
%IB
Off
-
On
1 - 100
%UB
1 - 100
%IB
1 - 100
%UB
Unit
1 - 12
-
Secondary system supervision
Step
Default
-
Off
-
UZsIZs
1
30
1
10
1
30
1
10
-
Off
1
60
1
15
1
70
1
10
-
On
1
70
1
5
1
60
Step
Default
1
1
Section 7
Description
Operation Off / On
Operating mode selection
Operate level of residual overvoltage
element in % of UBase
Operate level of residual undercurrent
element in % of IBase
Operate level of neg seq overvoltage
element in % of UBase
Operate level of neg seq undercurrent
element in % of IBase
Operation of change based function
Off/On
Operate level of change in phase voltage
in % of UBase
Operate level of change in phase current
in % of IBase
Operate level of phase voltage in % of
UBase
Operate level of phase current in % of
IBase
Seal in functionality Off/On
Operate level of seal-in phase voltage in
% of UBase
Operate level for open phase current
detection in % of IBase
Operate level for open phase voltage
detection in % of UBase
Description
Selection of one of the Global Base
Value groups
PID-3492-SETTINGS v9