Goose Binary Receive Goosebinrcv - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
13.3.12
13.3.12.1
13.3.12.2
508
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the APPxVAL output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the APPxVAL output will be LOW.

GOOSE binary receive GOOSEBINRCV

Function block
GOOSEBINRCV
BLOCK
^OUT1
^SRCOUT1
DVALID1
^SRCOUT2
^OUT2
^SRCOUT3
DVALID2
^SRCOUT4
^OUT3
^SRCOUT5
DVALID3
^SRCOUT6
^OUT4
^SRCOUT7
DVALID4
^SRCOUT8
^OUT5
^SRCOUT9
DVALID5
^SRCOUT10
^OUT6
^SRCOUT11
DVALID6
^SRCOUT12
^OUT7
^SRCOUT13
DVALID7
^SRCOUT14
^OUT8
^SRCOUT15
DVALID8
^SRCOUT16
^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST
IEC07000047-4-en.vsd
IEC07000047 V4 EN-US
Figure 242:
GOOSEBINRCV function block
Signals
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the Engineering Manual.
1MRK 511 424-UEN B
SEMOD173158-1 v3
SEMOD173175-4 v2
SEMOD173166-1 v2
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Bay control REC650 2.2 IEC
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents