Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 16
IED hardware
16.2.11.3
Table 554:
IRIG-B Non group settings (basic)
Name
SynchType
TimeDomain
Encoding
TimeZoneAs1344
16.2.11.4
678

Settings

Values (Range)
Unit
BNC
-
Opto
LocalTime
-
UTC
IRIG-B
-
1344
1344TZ
MinusTZ
-
PlusTZ
Technical data
Table 555:
IRIG-B
Quantity
Number of channels IRIG-B
Number of optical channels
Electrical connector:
Electrical connector IRIG-B
Pulse-width modulated
Amplitude modulated
– low level
– high level
Supported formats
Accuracy
Input impedance
Optical connector:
Optical connector IRIG-B
Type of fiber
Supported formats
Accuracy
Step
Default
-
Opto
-
LocalTime
-
IRIG-B
-
PlusTZ
Rated value
1
1
BNC
5 Vpp
1-3 Vpp
3 x low level, max 9 Vpp
IRIG-B 00x, IRIG-B 12x
+/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
100 k ohm
Type ST
62.5/125 μm multimode fiber
IRIG-B 00x
+/- 1μs
1MRK 511 424-UEN B
Description
Type of synchronization
Time domain
Type of encoding
Time zone as in 1344 standard
Bay control REC650 2.2 IEC
Technical manual
PID-5187-SETTINGS v5
SEMOD141132-1 v1
SEMOD141136-2 v9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents