Dead Line Detection - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
7.2.7.3
Bay control REC650 2.2 IEC
Technical manual
20 ms
20 ms
DeltaIL1
t
t
20 ms
20 ms
DeltaIL2
t
t
20 ms
20 ms
DeltaIL3
t
t
20 ms
DeltaUL1
t
20 ms
DeltaUL2
t
20 ms
DeltaUL3
t
IEC12000165 V1 EN-US
Figure 50:
Internal signals DeltaU or DeltaI and the corresponding output
signals

Dead line detection

A simplified diagram for the functionality is found in figure 51. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated