Function Block - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
13.7.6.3
13.7.6.4
Bay control REC650 2.2 IEC
Technical manual

Function block

I103FLTPROT
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
83_ZONE6
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291-2-en.vsdx
IEC10000291 V2 EN-US
Figure 258:
I103FLTPROT function block
Signals
Table 436:
I103FLTPROT Input signals
Name
Type
BLOCK
BOOLEAN
64_STL1
BOOLEAN
65_STL2
BOOLEAN
66_STL3
BOOLEAN
67_STIN
BOOLEAN
68_TRGEN
BOOLEAN
69_TRL1
BOOLEAN
70_TRL2
BOOLEAN
71_TRL3
BOOLEAN
72_TRBKUP
BOOLEAN
73_SCL
REAL
Table continues on next page
Station communication
Default
Description
0
Block of status reporting.
0
Information number 64, start phase L1
0
Information number 65, start phase L2
0
Information number 66, start phase L3
0
Information number 67, start residual current IN
0
Information number 68, trip general
0
Information number 69, trip phase L1
0
Information number 70, trip phase L2
0
Information number 71, trip phase L3
0
Information number 72, back up trip I>>
0
Information number 73, fault location in ohm
Section 13