ABB Relion 650 Series Technical Manual page 475

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
Bay control REC650 2.2 IEC
Technical manual
RSTACC
EAFPrestVal
ACCINPRG
P* (ACTIVE FORWARD)
60.0
1000 GWh
-1
q
= unit delay
IEC13000187 V5 EN-US
Figure 224:
Logic for integration of active forward energy
The energy pulses generated by using internally calculated accumulated energy
values and energy per pulse (ExxAccPlsQty) setting. The accumulated energy
values are divided by the energy-per-pulse value to get the number of pulses. The
number of pulses can be reset to zero by activating RSTACC input or by using the
local HMI reset menu. The pulse on and off time duration is set by the settings
tEnergyOnPls and tEnergyOffPls. Figure
generation for the integrated energy in the active forward direction. Similarly, the
pulse generation for integrated energy in the active reverse, reactive forward and
reactive reverse is done.
X
T
F
&
-1
0.0
q
a
a>b
b
225
shows the logic for pulse output
Section 11
Metering
T
F
-1
q
T
F
EAFACC
IEC13000187-5-en.vsdx
469

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec650

Table of Contents