Technical Data - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
9.13.7
9.14
9.14.1
9.14.2
Bay control REC650 2.2 IEC
Technical manual

Technical data

Table 256:
Number of IB16 instances
Function
3 ms
IB16
6
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
Identification
Function description
Integer to boolean 16 conversion with
logic node representation
Functionality
Integer to boolean conversion with logic node representation function (ITBGAPC)
is used to transform an integer which is transmitted over IEC 61850 and received
by the function to 16 boolean (logic) output signals.
ITBGAPC function can only receive remote values over IEC 61850 when the R/L
(Remote/Local) push button on the front HMI indicates that the control mode for
the operator is in position R (Remote i.e. the LED adjacent to R is lit), and the
corresponding signal is connected to the input PSTO ITBGAPC function block.
The input BLOCK will freeze the output at the last received value and blocks new
integer values to be received and converted to binary coded outputs.
Quantity with cycle time
8 ms
4
IEC 61850
IEC 60617
identification
identification
ITBGAPC
-
Section 9
Logic
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2
100 ms
8
SEMOD158419-1 v3
SEMOD167944-2 v4
ANSI/IEEE C37.2
device number
-
SEMOD158421-5 v9
337