Function Block - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
9.8.1.1
9.8.1.2
9.8.1.3
9.8.2
Bay control REC650 2.2 IEC
Technical manual

Function block

ANDQT
INPUT1
INPUT2
NOUT
INPUT3
INPUT4
IEC09000297-1-en.vsd
IEC09000297 V1 EN-US
Figure 149:
ANDQT function block
Signals
Table 205:
ANDQT Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Table 206:
ANDQT Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Technical data
Table 207:
Number of ANDQT instances
Logic block
3 ms
ANDQT
-
Single point indication related signals combining function
block INDCOMBSPQT
The value of single point input (SP_IN) is copied to the value part of the SP_OUT
output. The TIME input is copied to the time part of the SP_OUT output. State
input bits are copied to the corresponding state part of the SP_OUT output. If the
state or value on the SP_OUT output changes, the Event bit in the state part is
toggled.
OUT
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Description
Output signal
Inverted output signal
Quantity with cycle time
8 ms
20
Section 9
Logic
GUID-4CEE3C76-A39D-4C33-AD55-88C570210F2B v2
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3800-INPUTSIGNALS v6
PID-3800-OUTPUTSIGNALS v6
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
100 ms
100
GUID-13C9325D-D3A0-480F-9F3B-738A13E0ECF8 v3
GUID-EEBD65A5-394C-4ECD-BF6F-D556B610FC57 v3
313