SSCBR Non group settings (basic)
Name
Values (Range)
Operation
GlobalBaseSel
PhSel
RatedOperCurr
OperNoRated
RatedFltCurr
OperNoFault
tTrOpenAlm
tTrCloseAlm
OperAlmLevel
OperLOLevel
Table continues on next page
Bay control REC650 2.2 IEC
Technical manual
Table 322:
SSCBR Output signals
Name
OPENPOS
CLOSEPOS
INVDPOS
TRCMD
TRVTOPAL
TRVTCLAL
OPERALM
OPERLO
CBLIFEAL
MONALM
IPOWALPH
IPOWLOPH
SPCHALM
GPRESALM
GPRESLO

Settings

Unit
Off
-
On
1 - 12
-
Phase L1
-
Phase L2
Phase L3
100.00 - 5000.00
A
1 - 99999
-
500.00 - 99999.99
A
1 - 10000
-
0.000 - 0.200
s
0.000 - 0.200
s
0 - 9999
-
0 - 9999
-
Type
Description
BOOLEAN
CB is in open position
BOOLEAN
CB is in closed position
BOOLEAN
CB is in Invalid Position
BOOLEAN
Open command issued to CB
BOOLEAN
CB open travel time exceeded set value
BOOLEAN
CB close travel time exceeded set value
BOOLEAN
Number of CB operations exceeds alarm limit
BOOLEAN
Number of CB operations exceeds lockout limit
BOOLEAN
Remaining life of CB reduced to Life alarm level
BOOLEAN
CB 'not operated for long time' alarm
BOOLEAN
Accum I^CurrExponent integr over CB open
travel time exceeds alarm limit
BOOLEAN
Accum I^CurrExponent integr over CB open
travel time exceeds lockout limit
BOOLEAN
Spring charging time has crossed the set value
BOOLEAN
Pressure below alarm level
BOOLEAN
Pressure below lockout level
Step
Default
-
Off
1
1
-
Phase L1
0.01
1000.00
1
10000
0.01
5000.00
1
1000
0.001
0.040
0.001
0.040
1
200
1
300
Section 10
Monitoring
PID-3267-OUTPUTSIGNALS v10
Description
Operation Off / On
Selection of one of the Global Base
Value groups
Phase selection
Rated operating current of the breaker
Number of operations possible at rated
current
Rated fault current of the breaker
Number of operations possible at rated
fault current
Alarm level for open travel time
Alarm level for close travel time
Alarm level for number of operations
Lockout level for number of operations
PID-3267-SETTINGS v10