Settings - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 424-UEN B
11.2.5
Table 366:
ETPMMTR Non group settings (basic)
Name
Values (Range)
Operation
EnaAcc
tEnergy
tEnergyOnPls
Table continues on next page
Bay control REC650 2.2 IEC
Technical manual
Table 365:
ETPMMTR Output signals
Name
ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD

Settings

Unit
Off
-
On
Off
-
On
1 Minute
-
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
0.100 - 60.000
s
Type
Description
BOOLEAN
Accumulation of energy values in progress
BOOLEAN
Accumulated forward active energy pulse
BOOLEAN
Accumulated reverse active energy pulse
BOOLEAN
Accumulated forward reactive energy pulse
BOOLEAN
Accumulated reverse reactive energy pulse
BOOLEAN
Alarm for active forward energy exceed limit in
set interval
BOOLEAN
Alarm for active reverse energy exceed limit in
set interval
BOOLEAN
Alarm for reactive forward energy exceed limit in
set interval
BOOLEAN
Alarm for reactive reverse energy exceed limit in
set interval
REAL
Accumulated forward active energy value
REAL
Accumulated reverse active energy value
REAL
Accumulated forward reactive energy value
REAL
Accumulated reverse reactive energy value
REAL
Maximum forward active power demand value for
set interval
REAL
Maximum reverse active power demand value for
set interval
REAL
Maximum forward reactive power demand value
for set interval
REAL
Maximum reverse reactive power demand value
for set interval
Step
Default
-
Off
-
Off
-
1 Minute
0.001
1.000
Section 11
Metering
PID-6872-OUTPUTSIGNALS v3
Description
Operation Off/On
Activate the accumulation of energy
values
Time interval for energy calculation
Energy accumulated pulse ON time in
secs
PID-6872-SETTINGS v3