Bay control REC650 2.2 IEC
Technical manual
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
IEC 60870-5-103 vendor specific implementation
The signal and setting tables specify the information types supported by the IEDs
with the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in
the protection and control IED.
Be aware of that different cycle times for function blocks must be
considered to ensure correct time stamping.
Commands in control direction
Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 460:
I103IEDCMD supported indications
INF
Description
19
LED Reset
23
Activate setting group 1
24
Activate setting group 2
25
Activate setting group 3
26
Activate setting group 4
Function commands in control direction, pre-defined I103CMD
Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Table 461:
Pre-defined I103CMD supported indications
INF
Description
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
Section 13
Station communication