1MRK 511 424-UEN B
10.1.3
Bay control REC650 2.2 IEC
Technical manual
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual
hardware, (TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequence component
quantities:
I: sequence currents (positive, zero, negative sequence, amplitude and angle)
U: sequence voltages (positive, zero and negative sequence, amplitude and
angle).

Function block

The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
CVMMXN
I3P*
U3P*
S_RANGE
P_INST
P_RANGE
Q_INST
Q_RANGE
PF_RANGE
ILEAD
U_RANGE
I_RANGE
F_RANGE
IEC10000016-1-en.vsd
IEC10000016 V1 EN-US
Figure 171:
CVMMXN function block
CMMXU
I3P*
IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC05000699-2-en.vsd
IEC05000699 V2 EN-US
Figure 172:
CMMXU function block
S
P
Q
PF
ILAG
U
I
F
Section 10
Monitoring
SEMOD130334-4 v7
353