Signals - ABB Relion 650 Series Technical Manual

Bay control
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Logic
9.17.4
9.17.5
Table 273:
REALCOMP Group settings (basic)
Name
EnaAbs
RefSource
SetValue
SetValPrefix
EqualBandHigh
EqualBandLow
9.17.6
348

Signals

Table 271:
REALCOMP Input signals
Name
INPUT
REF
Table 272:
REALCOMP Output signals
Name
INEQUAL
INHIGH
INLOW
Settings
Values (Range)
Unit
Signed
-
Absolute
Set Value
-
Input REF
-999.999 - 999.999
-
milli
-
unit
kilo
Mega
Giga
0.10 - 10.00
%
0.10 - 10.00
%
Operation principle
The comparison can be done in two ways,
1.
Between 2 inputs, INPUT and REF
2.
Between INPUT and the SetValue setting
The selection of reference value for comparison can be done through setting
RefSource. If RefSource is selected as Input REF then the reference value for
Type
Default
Description
REAL
0.000
Input value to be compared with reference value
REAL
0.000
Reference value to be compared with input value
Type
Description
BOOLEAN
Input value is equal to the reference value
BOOLEAN
Input value is higher than the reference value
BOOLEAN
Input value is lower than the reference value
Step
Default
-
Signed
-
Set Value
0.001
0.001
-
unit
0.01
0.50
0.01
0.50
1MRK 511 424-UEN B
PID-6897-INPUTSIGNALS v2
PID-6897-OUTPUTSIGNALS v2
Description
Selection for absolute or signed
comparison
Selection for reference value either input
or setting
Set value for reference
Multiplication factor for SetValue
Equal band high limit in % of reference
value
Equal band low limit in % of reference
value
GUID-3FA699A8-D076-4E5E-BCB8-C6B7907573D1 v2
Bay control REC650 2.2 IEC
Technical manual
PID-6897-SETTINGS v2